Loading
A.C.B A.C.B 사양

A.C.B 사양

 형식  Model

SWB-8/M 

SWB-10/M 

SWB-12/M 

SWB-16/M 

SWB-20/M 

SWB-25,32/M

SWB-40/M 

  프레임 전류(A)  IEC, BS, VDE ,AS

  Frame Size(A)  JIS

                           JES

                           NEMA, ANSI

  800

  800

  800

  800

  1000

  1000

  1000

  1000

  1250

  1250

  1250

  1250

  1600

  1600

  1400

  1600

  2000

  2000

  2000

  2000

  2500  3200

  2500  3200

  2500  3200

  2500  3200

  4000

  4000

  4000

  4000

극수  Number of poles

2,3 / 4 

2.3 / 4 

2.3 / 4 

2.3 

2.3 / 4 

2.3 / 4 

2.3 / 4 

  과전류 트립장치의 1차 정격전류(A)

  * 일반산업용 적용

  Rated Current, In (Sensor Current)

  * Industrial Use

  80  100

  160  200

  320  400

  630  800

  250

  500

  1000

 

  320

  630

  1250

 

  1600

 

 

 

  250

  500

  1000

  2000

  2500   1600

              3200

 

 

  500

  1000

  2000

  4000

정격 절연전압(V) Insulation Voltage 

AC 660 

AC 660 

AC 660 

AC 660 

AC 660 

AC 660 

AC 660 

   정격 차단용량(KA.sym.) / 정격투입용량(KA)   Rated Breaking Capacity(KA.sym) / Rated Making Capacity(KA)

  IEC(P-2)순시트립 부착  AC 600V With Inst,

  Trip Device

  22/46.2

  22/46.2

  35/73.5

  35/73.5

  45/94.5

  45/94.5

  45/94.5

                                                      600V

  VDE                                             500V

                                                      415V

  30/63

  35/73.5

  35/73.5

  30/63

  35/73.5

  35/73.5

  50/105

  65/143

  65/143

  50/105

  65/143

  65/143

  50/105

  65/143

  65/143

  64/143

  85/187

  85/187

  65/143

  85/187

  85/187

  BS(P-2)                                       380V

                                                     240, 220V

  35/73.5

  35/73.5

  35/73.5

  35/73.5

  65/143

  65/143

  65/143

  65/143

  65/143

  65/143

  85/187

  85/187

  85/187

  85/187

  AS 순시트립 무부착                     AC 660V

  Without Inst. Trip Device          600V

                                                     up to 500V

  22/46.2

  30/63

  35/73.5

  22/46.2

  30/63

  35/73.5

  35/73.5

  50/105

  50/105

  35/73.5

  50/105

  50/105

  45/94.5

  50/105

  50/105

  45/94.5

  65/143

  65/143

  45/94.5

  65/143

  65/143

  NEMA 순시트립 부착                  AC 600V

  With Inst. Trip Device

  22/50.6

  22/50.6

  42/96.6

  42/96.6

  43/96.6

  50/115

  50/115

  ANSI                                           480V

                                                     240V

  30/69

  42/96.6

  30/69

  42/96.6

  50/115

  65/149.5

  50/115

  65/149.5

  50/115

  65/149.5

   65/149.5

   85/195.5

  65/149.5

  85/195.5

  순시트립 무부착 AC                    up to 600V

  Without Inst. Trip Device

  22/50.6

  22/50.6

  42/96.6

  42/96.6

  42/96.6

  50/115

  50/115

  ANSI                                           480V

                                                     240V

  30/69

  42/96.6

  30/69

  42/96.6

  50/115

  65/149.5

  50/115

  65/149.5

  50/115

  65/149.5

  65/149.5

  85/195.5

  65/149.5

  85/195.5

  순시트립 무부착 AC                    up to 600V

  Without Inst. Trip Device

  22/50.6

  22/50.6

  42/96.6

  42/96.6

  42/96.6

  50/115

  50/115

  JIS    순시트립                              AC 550V

  With Inst. Trip Device

  30/63

  30/63

  50/105

  50/105

  50/105

  65/143

  65/143

  JEC                                              460V

  Without Inst. Trip Device           220V

  순시트립 무부착                           AC 550V

                                                   up to 460V

  35/73.5

  35/73.5

  30/63

  35/73.5

  35/73.5

  35/73.5

  30/63

  35/73.5

  65/143

  65/143

  50/105

  50/105

  65/143

  65/143

  50/105

  50/105

  65/143

  65/143

  50/105

  50/105

  85/195.5

  85/195.5

  65/143

  65/143

  85/195.5

  85/195.5

  65/143

  65/143

  DC 정격차단용량(kA)                  DC 250V

  Rated Breaking Capacity(kA)

  40/40

  40/40

  40/40

  40/40

  40/40

  40/40

  40/40

  단시간 전류 RMS(kA)                      1s

  Shot Time withstand Current(kA) 3s

  35

  30

  35

  30

  50

  45

  50

  45

  50/

  45/

  65

  50

  65

  50

  Latching 전류 Current                RMS(kS)  35  35  50  50  50/  65  65
  전 차단 시간(S)    Breaking Time(S)  0.05  0.05  0.05  0.05  0.05  0.05  0.05
  정격 투입시간(S)   Closing Time(S) 
  스프링 축세시간(S)  Spring Charging Time  10  10  10  10  10  10  10
  투입시간(ms)   Closing Time(ms)  60  60  60  60  60  60  60